Extended limit-collapsed surfaces using fragility analysis of high voltage transmission towers located in coastal areas under wind load SCIE SCOPUS

Cited 0 time in WEB OF SCIENCE Cited 0 time in Scopus
Title
Extended limit-collapsed surfaces using fragility analysis of high voltage transmission towers located in coastal areas under wind load
Author(s)
Kwon, Kyungrok; Choi, Youngjin; Choi, Yangrok; Han, Whi Seok; Kim, Jeong Hun; Kong, Jung Sik
KIOST Author(s)
Choi, Youngjin(최영진)
Alternative Author(s)
최영진
Publication Year
2024
Abstract
Abstract When evaluating the fragility of structures in response to wind loads, vulnerability analyses are often conducted under intact conditions. Therefore, the actual strength of aged transmission towers may be compromised, resulting in severe damage. Especially for steel structures used over a long period in coastal areas, there is a potential for performance degradation due to corrosion. One of the high-voltage transmission towers, the 765 kV transmission tower, is taller than other towers, making it more vulnerable to strong winds in the event of corrosion. In this study, the structural performance degradation of 765 kV transmission towers in coastal regions based on their service life was investigated. Capacity distributions were provided considering the uncertainties in various parameters, such as the wind attack angle and material properties. A fragility assessment process that accounts for uncertainties in the wind conditions and aerodynamic pa- rameters is proposed. Using the research results, we created limit-collapsed surfaces to evaluate the structural safety of transmission towers based on their service life, wind speed, and wind attack angle. The results showed a quantitative decrease in structural safety due to corrosion depending on the service life, with the most unfavorable wind attack angle being 0°. The proposed limit-collapsed surface can help efficiently evaluate structural conditions considering wind speed, wind attack angle, and service life. Hence, this study can serve as a basis for the structural evaluation of modern transmission towers to avoid power disruptions in major cities.
ISSN
1369-4332
URI
https://sciwatch.kiost.ac.kr/handle/2020.kiost/45718
DOI
10.1177/13694332241263866
Bibliographic Citation
Advances in Structural Engineering, 2024
Publisher
Multi-Science Publishing Co Ltd.
Keywords
high-voltage transmission tower; limit-collapsed surface; wind attack angle; Coastal; corrosion; fragility